PROTECTIVE RELAY TESTING BASIC INFORMATION AND TUTORIALS
What is protective relay testing? How to do protective relay testing?
Protective relaying is a very broad subject. Only a brief overview can be given here. There are two major objectives in protective relaying.
First, a protective relay serves to provide equipment protection (i.e., locate and isolate overloads, short circuits, undervoltages, and other types of electrical problems quickly in order to minimize damage).
Second, the protective device that is closest to the problem should operate first to clear the problem, and no other device should operate unless the closest one fails. This concept, known as "selective tripping" or "selectivity", maintains service to as much of the electrical system as possible by isolating only the problem area.
In order to achieve these objectives, each relay must function as it was designed, and the relays must function in conjunction with the other protective devices in the system. Having all the protective devices function as one overall protective system is called "coordination".
Each protective device has specific parameters within which it has been designed to operate. For example, a single element fuse has a value of current above which it opens.
It takes a specific amount of time for a given current to melt the link away and open the fuse. Manufacturers of fuses publish "time-current" curves that show how long it takes a fuse to operate for varying current values.
Generally, the higher the current, the shorter the time.
This same inverse current-vs.-time concept is used for overcurrent relays and for low-voltage circuit breakers. Relays and low-voltage circuit breakers (with internal trip units) have a range of "pickup" operating current that causes them to operate.
In many cases, this value of current is adjustable. By properly selecting the type, characteristic, and/or setting of fuses, relays, or circuit breakers, the system can be coordinated so that the device that is closest to the problem opens before any device upstream of it. It is necessary to select compatible time current characteristics of the devices for the entire system, in addition to selecting the proper settings for the devices.
Prior to performing protective relay testing, a coordination study should be completed to determine the proper settings for the relays to be calibrated. This is usually done by the design engineer when the system is first installed. If there have been revisions or additions to the system, a new study may be necessary.
Once the coordination study has been completed, the relays need to be calibrated to the proper settings. There are special test sets available for this purpose that inject currents and voltages, as necessary, and time the various operations of the relays.
This type of testing is usually performed by a technician who specializes in this area. Depending upon the relay to be calibrated, quite complex test equipment may be required and in-depth training in protective relaying may be needed to properly set the relay.