SAFETY ENGINEERING | ELECTRICAL SAFETY | OSH ELECTRICAL | LIVE WIRE | HIGH VOLTAGE | HUMAN SAFETY
OVER CURRENT PROTECTIVE DEVICES FOR GENERATORS BASIC INFORMATION AND TUTORIALS
What are the basic overcurrent protection devices for generators?
As with other motors, NEC 445.11 requires a generator to have a nameplate giving the manufacturer’s name, the rated frequency, power factor, number of AC phases, the subtransient and transient impedances, the rating in kilowatts or kilovolt amperes, a rating for the normal volts and amps, rated revolutions per minute, insulation system class, any rated ambient temperature or temperature rise, and a time rating.
The size and type of OCPD will be based on this critical data. NEC 445.12 defines the basic overcurrent protection standards for various types of generators. A constant-voltage generator must be protected from overloads by either the generator’s inherent design or circuit breakers, fuses, or other forms of overcurrent protection that are considered suitable for the conditions of use.
This is true except for AC generator exciters.
Two-wire, DC generators are allowed to have overcurrent protection in only one conductor if the overcurrent device is triggered by the entire current that is generated other than the current in the shunt field. For this reason, the overcurrent device cannot open the shunt field.
If the two-wire generator operates at 65 V or less and is driven by an individual motor then the overcurrent device protection device needs to kick-in if the generator is delivering up to 150% of its full-load rated current.
When a two-wire DC generator is used in conjunction with balancer sets it accomplishes the neutral points for the three-wire system. This means it requires an overcurrent device that is sized to disconnect the three-wire system if an extreme unbalance occurs in the voltage or current.
For three-wire DC generators, regardless of whether they are compound or shunt wound, one overcurrent device must be installed in each armature lead, and must be connected so that it is activated by the entire current from the armature.
These overcurrent devices need to have either a double-pole, double-coil circuit breaker or a four-pole circuit breaker connected in both the main and equalizer leads, plus two more overcurrent devices, one in each armature lead.
The OCPD must be interlocked so that no single pole can be opened without simultaneously disconnecting both leads of the armature from the system.
The ampacity of the conductors that run from the generator terminals to the first distribution device that contains overcurrent protection cannot be less than 115% of the nameplate current rating for the generator per NEC 445.13.
All generators must be equipped with at least one disconnect that is lockable in the open position that will allow the generator and all of its associated protective devices and controls to be disconnected entirely from the circuits that are supplied by the generator.
Subscribe to:
Post Comments (Atom)
No comments:
Post a Comment